1 Scope
This part of IEC 60269 is applicable to fuses incorporating enclosed current-limiting fuse-links with rated breaking capacities of not less than 6 kA, intended for protecting power-frequency
AC circuits of nominal voltages not exceeding 1 000 V or DC circuits of nominal voltages
not exceeding 1 500 V.
Subsequent parts of this standard, referred to herein, cover supplementary requirements
for such fuses intended for specific conditions of use or applications.
Fuse-links intended to be included infuse-switch combinations according to IEC 60947‑3 should also comply with the following requirements.
As far as not stated in subsequent parts for fuse-links, details of performance (see 3.2.4) on DC circuits should be stated in the manufacturer's literature.
NOTE 1 Modifications of, and supplements to, this document required for certain types of
fuses for particular applications – for example, certain fuses for rolling stock, or fuses for high-frequency circuits – will be covered, if necessary, by separate standards.
NOTE 2 This document does not apply to miniature fuses, these being covered by IEC 60127.
The object of this standard series is to establish the characteristics of fuses or parts of fuses (fuse-base, fuse-carrier, fuse-link) in such a way that they can be replaced by other fuses or parts of fuses having the same characteristics provided that they are interchangeable as far as
their dimensions are concerned. For this purpose, this standard series refers in particular to