1 Scope
This document specifies the general requirements and tests for decomposition blockers
downstream of pressure regulators in acetylene manifold systems (see ISO 14114). Decomposition blockers can be used in the low-pressure section (downstream of acetylene
manifold system outlet) up to 0,15 MPa (1,5 bar) e.g. in pipelines, outlet points
or for the protection of low-pressure sections in big pipe systems. Decomposition
blockers can only be used in sections with pure acetylene. The possible backflow of
oxygen or air into the section where the decomposition blocker is installed needs
to be prevented by a non-return valve downstream of the decomposition blocker.