1 Scope
This document specifies a method for determining the fire resistance of vertical and
horizontal ventilation ducts under standardized fire conditions. The test examines
the behaviour of ducts exposed to fire from the outside (duct A) and fire inside the
duct (duct B). This document is intended to be used in conjunction with ISO 834‑1.
This document is not applicable to:
-
a) ducts whose fire resistance depends on the fire resistance performance of a ceiling;
-
b) ducts containing fire dampers at points where they pass through fire separations;
-
c) doors of inspection openings, unless included in the duct to be tested;
-
d) two-sided or three-sided ducts;
-
e) the fixing of suspension devices to floors or walls;
-
f) kitchen extract ducts (see ISO 6944‑2).
NOTE
Annex A provides general guidance and gives background information.