1 Scope
EN 50525‑3‑41
applies to non-sheathed single core cables insulated with halogen-free crosslinked
compound and having low emission of smoke and corrosive gases when exposed to fire.
NOTE 1 Low emission of smoke is checked in accordance with EN 61034‑2. Low emission of corrosive gases is checked as part of the check for absence of halogens
(see Annex B of EN 50525‑1).
The cables are of rated voltages U0/U up to and including 450/750 V.
NOTE 2 Cables rated 450/750 V may be used at 600/1 000 V when this cable is used in fixed
installations with mechanical protection, within switchgear and control gear - see
HD 516.
The cables are intended for fixed wiring applications.
The maximum conductor operating temperature for each of the cables in this standard
is 90 °C.
NOTE 3 HD 516 contains extensive guidance on the safe use of cables in this standard.
This EN 50525‑3‑41 should be read in conjunction with EN 50525‑1, which specifies general requirements.