1.1 General
This International Standard specifies a laboratory substitution method to determine
the insertion loss without flow of ducted, mainly absorbent, circular and rectangular
silencers, as well as other duct elements for use in ventilating and air-conditioning
systems.
NOTE 1 Laboratory measurement procedures for ducted silencers with superimposed flow are
described in ISO 7235.
This International Standard is applicable to silencers where the design velocity does
not exceed 15 m/s. As the method does not include self-generated flow noise, this
International Standard is not suitable for tests on silencers where this type of noise
is of great importance for the evaluation of the silencer performance.
The insertion loss determined according to this International Standard in a laboratory
will not necessarily be the same as the insertion loss that will be obtained in an
installation in the field. Different sound and flow fields in the duct will yield
different results. As this International Standard requires regular test ducts, the
results may include some flanking transmission via structural vibrations in the duct
walls, that sets an upper limit to the insertion loss that can be determined.
NOTE 2
ISO 7235
gives methods for determining this limit.
This International Standard is intended to be used for circular silencers with diameters
of 80 mm to 2 000 mm or rectangular silencers with crosssectional areas within the
same range.