1.1 General
This International Standard specifies a method for testing ducted fans and other air-moving
devices to determine the sound power radiated into an anechoically terminated duct
on the inlet and/or outlet side of the equipment.
NOTE 1 For the sake of brevity, wherever the term “fan” occurs in the text, it means “fan
or other air-moving device”.
The method is applicable to fans which emit steady, broad-band, narrow-band and discrete-frequency
sound and to air temperatures between – 50 °C and + 70 °C. The test duct diameter range is from 0,15 m to 2 m. Test methods for small (d < 0,15 m) and large (d > 2 m) test ducts are described in the informative Annexes H and I, respectively.
The maximum mean flow velocity at the microphone head for which the method is suitable
depends on the type of microphone shield used, and is as follows:
Above these values the suppression of turbulent pressure fluctuations by the microphone shield (see 3.9) may be insufficient.
It is expected that sound power tests will be conducted in conjunction with airflow
performance tests in accordance with ISO 5801. The ducting arrangement will therefore normally incorporate a “star” type flow straightener
on the outlet side of the fan which will minimize swirl (see 7.3). Where it is permissible to delete the straightener as, for example, with large
fans to installation category C according to ISO 5801:1997, the method is limited to a swirl angle of 15°. (An example of a method for determining
the angle of swirl is given in Annex J.)
NOTE 2 The installation categories defined in ISO 5801 imply that the fan is either ducted on the outlet side only (category B), on the
inlet side only (category C) or on both sides (category D).